7 Functions and settings
Maschinenfabrik Reinhausen 2014
96
222/08 EN
TAPCON® 240
Volts (V)
Kilovolts (kV)
This value relates to the secondary
voltage of the system's voltage
transformer.
This value relates to the primary
voltage of the system's voltage
transformer.
Table 19: Units available
If you want to change the display from
V
to
kV
, you have to set the trans-
former data of the device to be monitored.
To set the overvoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
V> regulator 2
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The overvoltage limit value is set as an absolute value.
Setting relative value
To set the overvoltage limit value of the voltage regulator to be monitored,
proceed as follows:
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
V< regulator 2.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The overvoltage limit value is set as a relative value.
Setting delay time for error message
You can use this parameter to set the delay time for the cross-monitoring er-
ror message. If an error is recorded by a monitoring device, the error mes-
sage is only displayed after the delay time .
To set the error message delay time, proceed as follows: