6 Commissioning
Maschinenfabrik Reinhausen 2014
49
222/08 EN
TAPCON® 240
Also refer to
2
2
Setting the Z compensation limit value [
Checking parallel operation
This section describes how you can run the function test for parallel opera-
tion.
To obtain perfect functioning in parallel operation, the voltage regulator must
be commissioned in simplex mode. Make sure that the conditions below
have been fulfilled.
▪
All devices are set to the same operating parameters for
desired value
,
circulating reactive current sensitivity
and
delay time T1
.
▪
The circulating reactive current sensitivity on all devices must be set to
0 %.
▪
The
circulating reactive current blocking
parameter must be set to
20 %.
▪
You must undertake all settings in manual mode.
▪
Each device needs an individual address on the CAN bus.
Checking circulating reactive current sensitivity
This section describes how to run the function test for circulating reactive
current sensitivity.
1.
Adjust both transformers in simplex mode to the same actual voltage by
means of the on-load tap-changer.
ð
When both devices are in a state of equilibrium, then the value of
the control deviation dV [%] is smaller than the set
bandwidth
. You
can see this in the main screen [
20] if the mark for the measured
voltage U
actual
is within the bandwidth.
2.
Connect the transformers in parallel and enable the parallel control.
ð
The two devices must still be in a state of equilibrium.
ð
The
Parallel operation
LED on the front panel is illuminated.
3.
On one of the two transformers, raise the tap position of the on-load tap-
changer by one setting; on the second transformer, lower the tap posi-
tion of the on-load tap-changer by one setting.
ð
The two devices must still be in a state of equilibrium.
4.
Adjust the
circulating reactive current sensitivity
until the result dis-
played exceeds the set value for the bandwidth by approx. 0.2 % to
0.3 %.
ð
The value for the result changes in the help text in the last line of
the display.
5.
Set the value given in the previous step for all devices in parallel opera-
tion.
6.3.3
Requirements
6.3.3.1
Summary of Contents for tapcon 240
Page 1: ...Voltage Regulator TAPCON 240 Operating Instructions 222 08 EN ...
Page 173: ......