Signal outputs
Relay
Inscription
Cause
IO-X1:23
CAN BE FREE-
LY PARAME-
TERIZED
0:OFF
1:MASTER FOLLOWER
2:LOCAL REMOTE
3:UNDERVOLTAGE
4:OVERVOLTAGE
5:DESIRED VALUE2
6:DESIRED VALUE3
7:TRIGGER MOTOR PROTECTIVE
SWITCH
8:MOTOR RUN TIME EXCEEDED
9:MOTOR RUNNING
10:ADVANCE RAISE SIGNAL
11:ADVANCE LOWER SIGNAL
IO-X1:25
CAN BE FREE-
LY PARAME-
TERIZED
0:OFF
1:MASTER FOLLOWER
2:LOCAL REMOTE
3:UNDERVOLTAGE
4:OVERVOLTAGE
5:DESIRED VALUE2
6:DESIRED VALUE3
7:TRIGGER MOTOR PROTECTIVE
SWITCH
8:MOTOR RUN TIME EXCEEDED
9:MOTOR RUNNING
10:ADVANCE RAISE SIGNAL
11:ADVANCE LOWER SIGNAL
IO-X1:21
FUNCTION
MONITORING
Signal for
Function monitoring
mes-
sage
IO-X1:10
AUTO
Signal if auto mode is active
IO-X1:09
MANUAL
Signal if manual mode is active
IO-X1:04
RAISE
Signal for raise switching pulse
IO-X1:06
LOWER
Signal for lower switching pulse
IO-X1:20
UNDERVOLT-
AGE
OVERVOLTAGE
OVERCURRENT
Signal for
undervoltage, overvoltage,
overcurrent
message
UC-X1:02
PARALLEL
FAULT
Signal for
parallel operation error
mes-
sage
UC-X1:04
PARALLEL ON
Signal if parallel operation is active
UC-
X1:06...10,
UC-
X1:19...27
TAP POSITION
BCD1…BCD20,
BCD+, BCD-
BCD signal of tap position
Table 43: Signal outputs