Figure 22: Recommended wiring
1
Cable duct for lines causing
interference
3
Cable duct for lines suscepti-
ble to interference
2
Interference-causing line (e.g.
power line)
4
Line susceptible to interfer-
ence (e.g. signal line)
▪
Short-circuit and ground reserve lines.
▪
The device must never be connected using multi-pin collective cables.
▪
Signal lines must be routed in a shielded cable.
▪
The individual conductors (outgoing conductors/return conductors) in
the cable core must be twisted in pairs.
▪
The shield must be fully (360º) connected to the device or a nearby
ground rail.
Using "pigtails" may limit the effectiveness of the shielding. Connect close-
fitting shield to cover all areas.