6 Commissioning
Maschinenfabrik Reinhausen 2014
51
222/08 EN
TAPCON® 240
7.
Press
to select auto mode.
ð
The motor-drive unit automatically returns to the original operating
position.
8.
Set the value determined for the
circulating reactive current blocking
on the devices in parallel operation as well.
If one or all devices indicate
Parallel operation error: circulating reactive cur-
rent limit exceeded
although the control inputs are correctly
connected for
all the devices, then all the devices block.
This could be due to various causes. Further information is given in the
chapter Troubleshooting [
ð
The function test for circulating reactive current blocking is complete.
Checking tap synchronization method
This section describes how to run the function test for tap synchronization
(master/follower). If instances arise where a follower switches in the opposite
direction to the master step change, then the setting for the tapping direction
[
63] parameter on the follower must be changed from
Default
to
Swap-
ped
.
NOTICE
Damage resulting from formation of circulating reactive current
If the parameters are not set correctly, damage may result from the forma-
tion of circulating reactive current and the resulting overload of transmission
lines and transformers.
► Check transformer type plate.
► Set device parameters in accordance with transformer configuration.
Before starting the function test, you must carry out the following steps:
1.
Assign the master function to one device.
2.
Assign the follower function to the other devices.