7 Functions and settings
Maschinenfabrik Reinhausen 2014
75
222/08 EN
TAPCON® 240
If one of the requirements listed below is not met, the active-power-depend-
ent desired value adjustment is not activated. Desired value 1, desired val-
ue 2 or desired value 3 is automatically used for regulation depending on
the setting.
▪
You must set the following parameters with valid values:
–
Power-dependent desired value must be set to
ON
–
Maximum active-power-dependent desired value
–
Minimum active-power-dependent desired value
–
Desired value at active power = 0
–
Active power at maximum desired value
–
Active power at minimum desired value
▪
A valid active power is measured
▪
A current transformer must be connected to measure the current
▪
A valid voltage is measured
Depending on device configuration, there are 3 ways in which the active-
power-dependent desired value adjustment can be activated/deactivated:
▪
On the device using the control panel
▪
REMOTELY using a control input on the IO card, UC1 card or UC2 card
▪
REMOTELY using SCADA
Activating/deactivating parameters on device
To activate or deactivate the power-dependent desired value adjustment,
proceed as follows:
1.
>
Parameter >
Control parameter > Press
until the
desired parameter is displayed.
ð
Power-dependent desired value.
2.
Press
or
to select the option you want.
3.
Press
.
ð
The power-dependent desired value adjustment is activated/deactivat-
ed.
Activating/deactivating parameters via a control input
Depending on configuration, you can also activate the active-power-depend-
ent desired value adjustment via an input on the following cards:
▪
IO card
▪
UC1 card
▪
UC2 card
Summary of Contents for tapcon 240