7 Functions and settings
Maschinenfabrik Reinhausen 2014
97
222/08 EN
TAPCON® 240
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
Error message.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The delay time is set.
Setting transformer for regulator 2
You use these parameters to set the transformer data of the device to be
monitored.
Setting the primary transformer voltage
The primary transformer voltage is set in kV.
To set the primary transformer voltage of voltage regulator 2, proceed as fol-
lows:
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
P.T. prim. voltage reg. 2.
2.
Press
to highlight the decimal place.
ð
The decimal place is defined and the value can be changed.
3.
Press
to increase the value or
to reduce it.
4.
Press
.
ð
The primary transformer voltage is set.
Setting the secondary transformer voltage
The secondary transformer voltage is set in V.
To set the secondary transformer voltage of voltage regulator 2, proceed as
follows:
1.
>
Parameter >
Cross-monitoring > Press
until the de-
sired parameter is displayed.
ð
P.T. sec. voltage reg. 2.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The secondary transformer voltage is set.