7 Functions and settings
Maschinenfabrik Reinhausen 2014
56
222/08 EN
TAPCON® 240
The voltage transformer's primary voltage is calculated by the device. For
correct functions, you must set the transformer data [
To change the desired unit for the voltage display, proceed as follows:
1.
Press
>
Configuration >
General >
until the desired
parameter is displayed.
ð
Display kV/V.
2.
Press
or
to select kV or V units.
3.
Press
.
ð
The required unit is set for the voltage display.
Setting current display unit
In this display, you can set the unit for the limit values displayed for overcur-
rent and undercurrent as a percentage ("%") or absolute value ("A").
It is only possible to change from % to A if all the transformer data have pre-
viously been entered.
To set the desired unit for the current display, proceed as follows:
1.
Press
>
Configuration >
General >
until the desired
parameter is displayed.
ð
Display %/A
2.
Press
or
to select % or A units.
3.
Press
.
ð
The required unit is set for the current display.
Setting the switching pulse time
You can use this parameter to set the duration of the switching pulse for the
motor-drive unit.
If you set the switching pulse time to 0 s, the motor-drive unit is activated
with a continuous signal. The signal then remains active for as long as the
or
keys are pressed.
If you set the switching pulse time to 1.5 seconds for example, after the set
delay time T1
or
delay time T2
there will be a switching pulse of 1.5 sec-
onds
.
7.2.4
7.2.5
Switching pulse in normal
mode