7 Functions and settings
Maschinenfabrik Reinhausen 2014
77
222/08 EN
TAPCON® 240
Setting maximum permissible power-dependent desired value
To set the maximum permissible power-dependent desired value, proceed
as follows:
1.
>
Parameter >
Control parameter > Press
until the
desired parameter is displayed.
ð
Maximum power-dependent desired value.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The maximum permissible power-dependent desired value is set.
Setting minimum permissible power-dependent desired value
To set the minimum permissible power-dependent desired value, proceed as
follows:
1.
>
Parameter >
Control parameter > Press
until the
desired parameter is displayed.
ð
Minimum power-dependent desired value.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The minimum permissible power-dependent desired value is set.
The following sections describe how to set the other parameters.
Setting desired value with active power 0
You can use this parameter to set the desired value which is to be used as
soon as the measured active power is 0.
You can enter the values in V or in kV. It is only possible to change from V
to kV if all the transformer data have previously been entered.
To set the desired value, proceed as follows:
1.
>
Parameter >
Control parameter > Press
until the
desired parameter is displayed.
ð
Desired value at 0 active power.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The desired value is set.
The following sections describe how to set the other parameters.