7 Functions and settings
Maschinenfabrik Reinhausen 2014
101
222/08 EN
TAPCON® 240
1.
>
Configuration >
Transformer data > Press
until the
desired parameter is displayed.
ð
Current transformer connection.
2.
Press
or
to select the required connection terminal.
3.
Press
.
ð
The current transformer connection is set.
Setting the phase difference for the current transformer/voltage
transformer
You can use this parameter to set the phase difference of the current trans-
former and voltage transformer. You can set the common transformer cir-
cuits as follows:
Tap-change
operation
Setting
Measurement
method
Phase differ-
ence
A
0 1PH
1 phase
0°
B
0 3PHN
3 phase
0°
C
0 3PH
3 phase
0°
D
90 3PH
3 phase
90°
E
30 3PH
3 phase
30°
F
-30 3PH
3 phase
-30°
Table 22: Set values for transformer circuit
Note the following sample circuits to select the correct transformer circuit.
Circuit A: 1-phase measurement in 1-phase grid
TAPCON® 240
Figure 59: Phase difference 0 1PH
▪
The voltage transformer VT is connected to the outer conductor and
neutral conductor.
▪
The current transformer CT is looped into the outer conductor.
▪
The voltage U
L1
and current I
L1
are in phase.
▪
The voltage drop on an outer conductor is determined by the current I
L1
.
7.8.5