6 Mounting
Maschinenfabrik Reinhausen GmbH 2020
52
4453918/14 EN
ETOS
®
TD
6 Mounting
This chapter describes how to correctly install and connect the device.
WARNING
Danger of death or severe injury!
An energized transformer and energized on-load tap-changer components
can cause death or serious injuries during installation of the drive!
► Ensure the de-energized state of the transformer and on-load tap-
changer components during installation of the drive.
6.1 Fitting the control cabinet to the transformer
Alternatively, you can secure the control cabinet to another point away from
the transformer. The supplied connection cable between the control cabinet
and the gear motor is 6.5 m long. If required, you can contact Maschinenfab-
rik Reinhausen GmbH for other lengths.
The control cabinet has four fixing attachments on the rear to secure it.
1. Attach four stud bolts (not supplied by MR) to the transformer tank.
Figure 32: Fastening the stud bolts
Type
A ± 15 mm
B ± 2 mm
S (850 mm)
575 mm
500 mm
L (1350 mm)
575 mm
500 mm
XL (1800 mm)
790 mm
1290 mm