9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
238
4453918/14 EN
ETOS
®
TD
▪ Additional, as an option:
– Duval analysis
– Rogers analysis
– Dörnenburg analysis
– IEC 60599 analysis
9.27.1 Configuring DGA monitoring
For the DGA monitoring "DGA", you can set 3 limit values for the absolute
values and for the rates of increase. Depending on the device configuration,
you can monitor up to 11 DGA signals. You can also set the following pa-
rameters:
▪ Sensor measuring accuracy
▪ Reset diagnostic errors
▪ Rates of increase evaluation interval
▪ Relative moisture in oil default value
▪ Use relative moisture in oil default value
Settings
Parameters
DGA monitoring
Name
Value
Measuring accuracy of the sensor
15.0 %
Reset diagnostic error memory
Off
Evaluation interval for rates of ...
7 days
C2H2 >
1.0 ppm
C2H2 >>
10.0 ppm
C2H2 >>>
35.0 ppm
C2H4 >
50.0 ppm
C2H4 >>
100.0 ppm
C2H4 >>>
200.0 ppm
C2H6 >
65.0 ppm
C2H6 >>
100.0 ppm
C2H6 >>>
150.0 ppm
CH4 >
120.0 ppm
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 172: Configuring DGA monitoring
To set the DGA monitoring, proceed as follows:
1. Go to
Settings > Parameters > DGA monitoring
.
2. Select the desired parameter.
3. Set parameter.
4. Press the
Accept
button to save the modified parameter.
Sensor measuring accuracy
You can use this parameter to enter the sensor measuring accuracy as a
percentage value. When doing so, refer to the sensor operating instructions.