9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
300
4453918/14 EN
ETOS
®
TD
On
Off
Input
Output
FALSE
TRUE
FALSE
Figure 222: Analog threshold value switch with the On Limit > Off Limit setting
Off
On
Input
Output
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
Figure 223: Analog threshold value switch with the On Limit < Off Limit setting
9.38.1.3.14 Analog multiplication
Description
MUL, analog multiplication
Inputs
Value (REAL32)
Multiplier (REAL32)
Outputs
Result (REAL32)
Overflow (BOOL)
Parameter
Constant multiplier (REAL32), -1,000,000...+1,000,000;
default = 1
Function
Result = Value * Multiplier * Constant multiplier
If the REAL32 range of numbers is exceeded, the
Overflow output becomes TRUE.
Initial state
All inputs and outputs are zero or FALSE.
Table 109: Analog multiplication function module