9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
264
4453918/14 EN
ETOS
®
TD
9.31.3 Undertaking and confirming maintenance
Once you have undertaken maintenance, you can confirm this on the device
and thereby reset the maintenance interval. The following maintenance pa-
rameters can be entered based on the maintenance type:
Value
Description
Date
Date of maintenance.
Operations counter
Reading of the operations counter at the time of mainte-
nance.
You can enter the current counter reading or a smaller
counter reading.
Contact wear (only
OILTAP®)
▪ MSCA
▪ MSCB
▪ TC1A
▪ TC1B
▪ TC2A
▪ TC2B
Overall contact wear on the stationary contact and moving
contact.
If you have measured the contact wear during mainte-
nance and continue to use the contacts in their original
positions, then enter the measured values and select "No"
in the prompt that reads "Contacts exchanged/replaced"
to confirm it. This causes the monitoring system to opti-
mize its calculation model and subsequent calculation of
the contact wear is more precise.
If you have exchanged (other position) or replaced con-
tacts, then enter the contact wear found on the mounted
contacts (for new contacts: 0.000 mm) and select "Yes" in
the prompt that reads "Contacts exchanged/replaced" to
confirm it.
Table 85: Maintenance parameters