9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
176
4453918/14 EN
ETOS
®
TD
9.18 Measurement
You can use the following parameters to configure the measurement of cur-
rent and voltage.
Settings
Parameters
Measurement
Name
Value
Regulation mode
Single-phase
Control variable
L1/N or L1/L2
UI measuring channels
3-phase measurem.: Ch. 1,2,3
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 116: Measurement
1. Go to
Settings > Parameters > Grid > Measurement
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
9.18.1 UI measuring channels
If you are measuring the voltage and current with the 3-phase UI 3 measur-
ing module, you can use this parameter to set the measurement channels in
use:
Option
Description
1-ph. measurement: Channel 1
The device uses 1 channel each for measure-
ment of voltage and current.
3-ph. measurement: Channel 1,
2, 3
The device uses 3 channels each for measure-
ment of voltage and current.
3-ph. voltage, 1-ph. current
The device uses 3 channels for voltage measure-
ment and 1 channel for current measurement.
Table 61: UI measuring channels