12 Event messages
Maschinenfabrik Reinhausen GmbH 2020
321
4453918/14 EN
ETOS
®
TD
No.
Name
Description
Remedy
1076 Gen. temperature 7 >
limit value
Generic temperature 7 is greater
than > limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1077 Gen. temperature 7 >>
limit value
Generic temperature 7 is greater
than >> limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1078 Gen. temperature 7 <
limit value
Generic temperature 7 is less
than < limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1079 Gen. temperature 7 <<
limit value
Generic temperature 7 is less
than << limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1080 Gen. temperature 8 >
limit value
Generic temperature 8 is greater
than > limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1081 Gen. temperature 8 >>
limit value
Generic temperature 8 is greater
than >> limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1082 Gen. temperature 8 <
limit value
Generic temperature 8 is less
than < limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1083 Gen. temperature 8 <<
limit value
Generic temperature 8 is less
than << limit value.
Check the current operating conditions of the
transformer, temperature sensor, analog signal
configuration, and the set limit value.
1086 Hot-spot > limit value
Hot-spot temperature is greater
than > limit value.
Check the current operating conditions of the
transformer, the parameters for calculating the
hot-spot temperature, and the set limit value.
1087 Hot-spot >> limit value
Hot-spot temperature is greater
than >> limit value.
Check the current operating conditions of the
transformer, the parameters for calculating the
hot-spot temperature, and the set limit value.
1088 Aging rate > limit value Aging rate is greater than > limit
value.
Check the current operating conditions of the
transformer, the parameters for calculating the
aging rate, and the set limit value.
1089 Aging rate >> limit
value
Aging rate is greater than >> limit
value.
Check the current operating conditions of the
transformer, the parameters for calculating the
aging rate, and the set limit value.
1095 OLTC oil level >> limit
value
Oil level of on-load tap-changer is
greater than >> limit value.
Check the on-load tap-changer oil level and the
device wiring. If using an analog sensor, check
the sensor, analog signal configuration, and the
set limit value.
1097 OLTC oil level << limit
value
Oil level of on-load tap-changer is
less than << limit value.
Check the on-load tap-changer oil level and the
device wiring. If using an analog sensor, check
the sensor, analog signal configuration, and the
set limit value.
1099 Transformer oil level
>> limit value
Oil level of transformer is greater
than >> limit value.
Check the transformer oil level and the device
wiring. If using an analog sensor, check the sen-
sor, analog signal configuration, and the set limit
value.