9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
95
4453918/14 EN
ETOS
®
TD
ASDU address
You can use this parameter to set the address of the ASDU.
ASDU sequence optimization
With this parameter, you can set which method is to be used for optimizing
the ASDU types. The standard enables optimization in order to be able to
transfer multiple value changes in a telegram in a sequence of ascending in-
formation object addresses. This is displayed by the sequence bit. The se-
lection of ASDU types for which this optimization is allowed is based on the
edition of the standard.
You can select the following options:
Option
Description
None
The device does not optimize the ASDU types.
Ed. 1
Optimization in accordance with IEC 60870 Edition 1
(Type 1, 3, 9, 11, 21, 126).
Ed. 1 Amendment2
Optimization in accordance with IEC 60870 Edition 1,
Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126).
Ed. 2
Optimization in accordance with IEC 60870 Edition 2
(Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126).
Table 27: ASDU sequence optimization
Reference time
You can use this parameter to set which time is to be transmitted by the con-
trol system. The device uses this information for time synchronization
[
Section 9.5, Page 83]. You can select the following options:
Option
Description
Local
The control system transmits the local time.
Page 84]. Otherwise the device will use
an incorrect time.
UTC
The control system transmits the time as UTC. The de-
vice calculates the local time from UTC and the set time
zone [
Table 28: Reference time
IP address Client 1/2/3 (optional)
If you use the optional "Multi-client" function, you can use these parameters
to set the IP addresses of the SCADA clients. The device only accepts com-
mands through the control system from end devices that have their IP ad-
dresses set here.