9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
141
4453918/14 EN
ETOS
®
TD
The device only processes commands via digital inputs or the control sys-
tem when it is in the Remote mode. You must also set the Remote behavior
[
Page 76] parameter accordingly.
Setting the desired value
1. Go to
Settings > Parameters > Grid > Control > Desired value
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
Selecting a desired value
You can use this parameter to select the desired value used for control.
1. Go to
Settings > Parameters > Grid > Control > Select desired value
.
2. Select the desired value from the list.
3. Press the
Accept
button to save the modified parameter.
9.15.1.3 Desired value 1...5
You can set 5 different desired values. The device always uses one of the
set desired values for control. You can define the desired value used for
control by means of the "Select desired value" parameter or with the digital
inputs.
The device only processes commands via digital inputs or the control sys-
tem when it is in the Remote mode. You must also set the Remote behavior
[
Page 76] parameter accordingly.
Setting the desired value
1. Go to
Settings > Parameters > Grid > Control > Desired value
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
Selecting a desired value
You can use this parameter to select the desired value used for control.
1. Go to
Settings > Parameters > Grid > Control > Select desired value
.
2. Select the desired value from the list.
3. Press the
Accept
button to save the modified parameter.