9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
87
4453918/14 EN
ETOS
®
TD
Severity level
Description
Notice
Notice state
Info
Information state
Debug
Debug state
Table 21: Severity levels
9.7 SCADA
The following section describes how you can configure the device to connect
to a control system (SCADA). You can download the data points with the
help of the export manager [
9.7.1 Configuring IEC 61850 (optional)
If you want to use the IEC 61850 control system protocol, you must set the
following parameters. Also refer to the section Configuring the network
[
Settings
Parameters
IEC 61850
Name
Value
IED name
TAPCON
Device ID
TAPCON
Access point
MRTCAP
Edition
Edition 1
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 64: IEC 61850
1. Go to
Settings > Parameters > System > IEC 61850
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
IED name
You can use this parameter to assign the device an IED name in order for it
to be identified in the IEC 61850 network.
The IED name must start with a letter and may contain no more than 11
characters.