12 Event messages
Maschinenfabrik Reinhausen GmbH 2020
317
4453918/14 EN
ETOS
®
TD
No.
Name
Description
Remedy
295 Tap position display er-
ror
The module for the tap position
display is defective.
Check the module for the tap position display.
296 Communication with
tap position display er-
ror
A connection with the module for
the tap position display cannot be
established.
Check the connection cable between the control
and module for the tap position display.
297 Deviation in tap posi-
tion
A deviation in the tap position has
been detected.
The tap positions of the control and module for
the tap position display are different. An auto-
matic adjustment is undertaken.
298 Deviation in operations
counter
A deviation in the operations
counter has been detected.
The operations counters for the control and
module for the tap position display are different.
An automatic adjustment is undertaken.
299 OLTC: Mechanical
blocking
The on-load tap-changer is me-
chanically blocked.
Check the on-load tap-changer.
300 Motor voltage invalid
Voltage of the motor is invalid.
Check connection of the motor voltage mea-
surement card.
301 Generic SCADA com-
mand 1
The generic SCADA command 1
has been received.
-
302 Generic SCADA com-
mand 2
The generic SCADA command 2
has been received.
-
303 Generic SCADA com-
mand 3
The generic SCADA command 3
has been received.
-
304 Generic SCADA com-
mand 4
The generic SCADA command 4
has been received.
-
305 Generic SCADA com-
mand 5
The generic SCADA command 5
has been received.
-
306 Generic SCADA com-
mand 6
The generic SCADA command 6
has been received.
-
307 Generic SCADA com-
mand 7
The generic SCADA command 7
has been received.
-
308 Generic SCADA com-
mand 8
The generic SCADA command 8
has been received.
-
309 Generic SCADA com-
mand 9
The generic SCADA command 9
has been received.
-
310 Generic SCADA com-
mand 10
The generic SCADA command 10
has been received.
-
311 Generic digital input 1
There is a signal at the generic
digital input 1.
-
312 Generic digital input 2
There is a signal at the generic
digital input 2.
-
1001 Ambient temperature
invalid
The analog signal for recording
the ambient temperature is in-
valid.
Check the sensor, device wiring, and analog
signal configuration.
1002 Lower oil temperature
invalid
The analog signal for recording
the lower oil temperature is in-
valid.
Check the sensor, device wiring, and analog
signal configuration.