12 Event messages
Maschinenfabrik Reinhausen GmbH 2020
316
4453918/14 EN
ETOS
®
TD
No.
Name
Description
Remedy
186 Tap position analog
output
The value cannot be output via
the analog output.
Check the parameter settings and the wiring of
the analog output.
259 Phase sequence incor-
rectly connected
Phase sequence incorrectly con-
nected
Check whether the motor is correctly connected
to the power supply (note rotary field!).
260 Limit value ∆U-3ph
The limit value for the difference
in voltage between the three
phases is exceeded.
Check the current operating conditions of the
transformer and the set parameter ∆U-3ph.
263 Limit value ∆f-3ph
The limit value for the angle dif-
ference between the three
phases is exceeded.
Check the current operating conditions of the
transformer and the set parameter ∆f-3ph.
266 Measuring connection
or configuration faulty
The connection and/or configura-
tion of the three-phase measure-
ment is faulty.
Inspect the connection of the current trans-
former and voltage transformer and the configu-
ration of the three-phase measurement.
267 cosf interpolation ac-
tive
The parallel operation is carried
out with interpolated values.
No CAN bus communication with other
TAPCON® present. Check wiring as per con-
nection diagram.
271 Signal from gear motor
missing
No feedback from gear motor
(S13)
Ensure that the gear motor is correctly con-
nected to the control cabinet. Check the func-
tionality of the cam switch S13.
276 Protective relay RS of
OLTC column A trig-
gered
The protective relay RS of the on-
load tap-changer (column A) has
triggered.
Contact Maschinenfabrik Reinhausen GmbH's
Technical Service department.
279 Pressure relief device
of OLTC column A trig-
gered
The pressure relief device of the
on-load tap-changer (column A)
has triggered.
Contact Maschinenfabrik Reinhausen GmbH's
Technical Service department.
282 Pressure relief device
of transformer trig-
gered
The pressure relief device of the
transformer has triggered
Establish the cause of the pressure relief device
triggering.
283 Buchholz relay: Accu-
mulation of gases (col-
umn A)
The Buchholz relay of the on-load
tap-changer (column A) is report-
ing the accumulation of gases.
Establish the cause of gases accumulating.
286 Buchholz relay: Loss of
insulating fluid (column
A)
The Buchholz relay of the on-load
tap-changer (column A) is report-
ing a loss of insulation fluid.
Establish the cause of the loss of insulating
fluid.
289 Buchholz relay: Insu-
lating fluid surge (col-
umn A)
The Buchholz relay of the on-load
tap-changer (column A) is report-
ing a sudden surge in insulating
fluid.
Establish the cause of the surge in insulating
fluid.
292 Buchholz relay: Accu-
mulation of gases
(transformer)
The Buchholz relay of the trans-
former is reporting the accumula-
tion of gases.
Establish the cause of gases accumulating.
293 Buchholz relay: Loss of
insulating fluid (trans-
former)
The Buchholz relay of transformer
is reporting a loss of insulation
fluid.
Establish the cause of the loss of insulating
fluid.
294 Buchholz relay: Insu-
lating fluid surge
(transformer)
The Buchholz relay of the trans-
former is reporting a sudden
surge in insulating fluid.
Establish the cause of the surge in insulating
fluid.