9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
275
4453918/14 EN
ETOS
®
TD
Events
No.
Event
Time
8
Limit value I>>
17.03.2020
10:56:59/669
12
Limit value S>>
16
Limit value P>>
18
Limit value Q<<
1001
Ambient temperature invalid
1002
Ambient temperature
17.03.2020
10:56:59/669
17.03.2020
10:56:59/669
17.03.2020
10:56:59/669
17.03.2020
10:56:59/669
17.03.2020
3
12
38
Log
Confirm
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.03.2020 08:08
Figure 208: Overview of events currently active
Acknowledging events
Acknowledgeable events must be acknowledged in the event overview so
that they are no longer displayed. All other events are automatically removed
once the cause is remedied (e.g. limit value no longer infringed).
To acknowledge the events, proceed as follows:
► To acknowledge the events, highlight the desired events in the
column
then press the
Acknowledge
button.
ð
The events are acknowledged.
9.33.2 Configuring events
The events have the following properties:
Property
Description
Event name
Brief name of event. If you delete all of the text, the stan-
dard text is displayed.
Event description
Description of event. If you delete all of the text, the stan-
dard text is displayed.
Event troubleshooting
Instructions for troubleshooting the cause of an event. If
you delete all of the text, the standard text is displayed.
Category
▪ Error (red)
▪ Warning (yellow)
▪ Info (gray)
This setting affects the color of the
Alarm
LED and the
event symbol in the primary navigation.
Report
If you activate this option, the event is shown on the dis-
play and, if configured accordingly, issued via an output
and the control system protocol.