9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
98
4453918/14 EN
ETOS
®
TD
9.7.6 Configuring DNP3 (optional)
If you would like to use the DNP3 control system protocol, you must set the
parameters listed below. Also refer to the section Configuring the network
[
Section 9.3, Page 79] if you want to use the DNP3 via TCP.
Settings
Parameters
DNP3
Name
Value
DNP3 transmission type
TCP
TCP port
20000
Device address
1
Timeout for response confirmation
5 s
Unsolicited messages
Off
Destination address
10000
Timeout confirmation
5 s
Indefinite unsolicited retries
Off
Number of unsolicited retries
3
User ID code
ISM
Reference time
UTC
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
31.01.2020 13:05
Figure 69: DNP3
1. Go to
Settings > Parameters > System > DNP3
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
9.7.6.1 DNP3 transmission type
You can use this parameter to set the transmission type. You can select the
following options:
▪ TCP
▪ Serial
TCP port
You can use this parameter to set the TCP port.
Serial interface
You can use this parameter to select the serial interface for data transmis-
sion. You can select the following options:
▪ RS232
▪ RS485
Summary of Contents for ETOS TD
Page 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Page 330: ......
Page 332: ......
Page 334: ......
Page 355: ......