9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
252
4453918/14 EN
ETOS
®
TD
Adding a sensor definition
You have to set the following values to add a sensor:
Value
Description
Sensor name
Entry field, max. 20 characters
Sensor version
Format:
X.Y.Z
(e.g. 1.5.2), used together with the sensor
name to provide unique identification of the sensor in the
sensor management menu.
Sensor manufacturer
(optional)
Entry field, max. 15 characters
Data points
Configuration of the sensor data points
Table 81: Adding sensors
The operation described below is only possible if you access the visualiza-
tion using a computer. You must also have a Parameterizer or Administrator
user role.
Proceed as follows to add a sensor:
1. Go to
Settings > Sensor bus > Sensor editor
.
2. Press the
New sensor
button.
Figure 186: Defining a new sensor
3. Enter the
sensor name
,
sensor version
and
sensor manufacturer
(op-
tional).
4. Press the
Accept
button to save the settings and configure the data
points.
Configuring data points
You must set the following values to configure a data point:
▪ Type
– IREG: Input register (analog input)
Summary of Contents for ETOS TD
Page 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Page 330: ......
Page 332: ......
Page 334: ......
Page 355: ......