9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
241
4453918/14 EN
ETOS
®
TD
9.27.2 Displaying measured values
The overview screen displays the current status of the dissolved gas analy-
sis.
Figure 173: Overview screen
Depending on the analysis method, the following status values are dis-
played:
Value
Description
Gray
Limit value not exceeded
Yellow
Yellow limit exceeded
Red
Red limit exceeded
Table 78: Status values for absolute values and rates of increase
Value
Description
Duv.
Rog.
Dörn.
IEC
--
Analysis not possible
+
+
+
+
N
Normal operation
-
+
-
-
D1
Discharge of low energy
+
+
-
+
D2
Discharge of high energy
+
+
+
+
D1/D2
Discharge of low/high energy
-
-
-
+
T1
Thermal fault <300 °C
+
+
-
+
T2
Thermal fault 300...700 °C
+
+
-
+
T3
Thermal fault >700 °C
+
+
-
+
PD
Partial discharge
+
-
+
+
TD
Mixed thermal/electrical fault
+
-
-
-
T1-T3
Thermal decomposition
-
-
+
-
Table 79: Status values for the Duval, Rogers, Dörnenburg and IEC 60599 analyses
Summary of Contents for ETOS TD
Page 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Page 330: ......
Page 332: ......
Page 334: ......
Page 355: ......