2 Safety
Maschinenfabrik Reinhausen GmbH 2020
20
4453918/14 EN
ETOS
®
TD
Hearing protection
To protect against hearing damage.
Protective gloves
To protect against mechanical, thermal, and electrical
hazards.
Table 5: Personal protective equipment
2.6 Drying transformer
2.6.1 Drying transformer in autoclave
Observe the following information when drying the transformer in an auto-
clave.
NOTICE
Damage to drive and on-load tap-changer/de-energized tap-
changer!
If the drive is dried in an autoclave, the drive and on-load tap-changer/de-
energized tap-changer may be damaged.
► Do not dry drive in an autoclave.
► Remove on-load tap-changer head cover with gear motor before drying.
To do so, follow the operating instructions of the on-load tap-changer. Do
not remove gear motor from the on-load tap-changer head cover.
2.6.2 Drying transformer in its own tank
If you dry the transformer in its own tank, the drive can remain attached to
the transformer during drying.