[7-1 Error Code and Preliminary Error Code Lists ]
HWE18220_GB
chapter 7 -
5
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
The last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indicate if the codes apply to inverter
on fan inverter.
Example
Code 4225 (detail code 108): Bus voltage drop in the fan inverter system
Code 4230 : Heatsink overheat protection in the inverter system
<Compressor inverter>
<Fan inverter>
The last digit
Inverter system
0 or 1
Compressor inverter system
5 or 6
Fan inverter system
INV board
Outdoor units
Overload protec-
tion Imax (Arms)
Current effective
value error (Arms)
Current peak value
error (Apeak)
Temperature
protection TOL (°C)
INV42Y
HP72YNU
27
33
56
95
INV42Y
HP96YNU
INV42Y
HP120YNU
INV38
HP72TNU
48
58
99
95
INV38
HP96TNU
51
61
104
INV38
HP120TNU
INV board
Outdoor units
Overload protec-
tion Imax (Arms)
Current peak value
error (Apeak)
INV/S15Y
HP72YNU
4.5
8.5
HP96YNU
HP120YNU
INVS/16Y
HP72TNU
6.5
12
HP96TNU
HP120TNU