[8-11 Control Circuit ]
60
-
chapter 8
HWE18220_GB
8 Troubleshooting Based on Observed Symptoms
YES
NO
414-506 VAC
NO
YES
Is there conductivity between them?
A
B
YES
NO
Any problems with wiring or
loose connectors?
Correct wiring problems, and tighten loose connectors.
Replace the power-supply board.
YES
Any loose
screws?
NO
Tighten loose screws.
Replace the noise filter
Check the power-supply wiring and the main
power supply, and correct any problems found.
Turn the power
supply back on.
Check the wiring between the noise filter board and
TB1 of power supply terminal block for proper
connections.
Check the voltage across L1 and L2 of power supply
terminal block TB1.
Check for conductivity between TB11 and TB21 and
between TB12 and TB22.
Check TB11, TB12, TB21, TB22 on the noise
filter for loose screws.