[8-10 Troubleshooting Inverter Problems ]
48
-
chapter 8
HWE18220_GB
8 Troubleshooting Based on Observed Symptoms
8-10-6
Checking the Fan Motor for Ground Fault and Coil Resistance Problems
8-10-7
Checking the Fan Board Error Detection Circuit at No Load
8-10-8
Checking the Fan Board for Damage at No Load
Items to be checked
Phenomena
Remedy
Remove fan motor winding. Check
insulation resistance and coil resis-
tance.
1)
Fan motor insulation failure.
If < 1 M
ȍ
, Defect.
Change fan motor.
2)
Fan motor wire failure.
Target coil resistance: Approx. 10
ȍ
.
(Changes with temperature)
Change fan motor.
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than current sensor er-
ror (5305, 5306: Detail code 135) is
detected during operation.
Replace the fan board.
(2)
Disconnect the output wiring
to the fan motor.
Disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
2)
Current sensor fault
Error code: 5305, 5306
Detail code: 135
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(3)
Turn on the breaker.
(4)
Operate the unit.
Items to be checked
Phenomena
Remedy
(1)
Stop the unit.
Turn off the breaker.
*Be sure to turn off the power.
1)
An error other than the current sen-
sor error (5305, 5306 Detail code
135) is detected within 30 seconds
from the startup of operation.
Replace the fan board.
(2)
To allow for the disconnection
of output wiring from the fan
motor, disconnect connector
RYFAN1. (On a model with
two fan motors, RYFAN1 cor-
responds to the right fan and
RYFAN2 corresponds to the
left fan (when seen from the
front).)
2)
Inter-wire voltage imbalance of 5 V or
above
Replace the fan board.
(3)
Set SW7-2 on the control
board to ON. On a model with
two fan motors, set SW7-2
(left fan when seen from the
front) or SW7-4 (right fan
when seen from the front) to
ON.
3)
No inter-wire voltage imbalance ex-
ists. A current sensor error (Detail
code 135) is detected 30 seconds af-
ter the startup of operation, and the
operation stops.
Normal
*When done checking, reconnect all
connectors as they were. Unless
they are properly reconnected, cur-
rent sensor fault will not be resolved.
(4)
Turn on the breaker.
(5)
Operate the unit
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......