[5-1 Dipswitch Functions and Factory Settings ]
HWE18220_GB
chapter 5 -
9
5 Control
(2) ME remote controller (PAR-F27MEA-US)
Set the address of the remote controller with the rotary switch.
To set addresses, use a precision slotted screw driver [(-), 2.0 mm [0.08 in] (w)], and do not apply than 19.6N.
The use of any other tool or applying too much load may damage the switch.
The ME remote controllers (PAR-U01MEDU) do not have the switches listed above. Refer to the installation manual for the
function setting.
012
3
45
67
8
9
012
3
45
67
8
9
012
3
45
67
8
9
012
3
45
67
8
9
10's digit 1's digit
(left)
(right)
Remote controller unit
Rotary switch
Example: In case of address 108
Address setting range
Setting method
Main remote controller
101-150
Add 100 to the smallest address of all the indoor units in the
same group.
Sub remote controller
151-200
Add 150 to the smallest address of all the indoor units in the
same group.
Setting of rotary switch
Address No.
01-99
*1
101-199 with the 100's digit automatically being set to 1
*2
00
200
*1. At factory shipment, the rotary switch is set to 01.
*2. The address range that can be set with the ME remote controller is between 101 and 200. When the dials are set to
a number between 01 and 99, the 100's digit is automatically set to [1]. When the dials are set to 00, the 100's digit is
automatically set to [2].
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......