[2-1 System Configurations ]
HWE18220_GB
chapter 2 -
1
2 Restrictions
2 Restrictions
2-1
System Configurations
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
3) Standard units and high-COP units cannot be used in combination.
Outdoor units
Composing units
Maximum total ca-
pacity of connect-
able indoor units
Maximum num-
ber of connect-
able indoor units
Types of connectable in-
door units
HP72T/YNU-A
-
-
36 - 108
18
P05 - P96 models
R410A series indoor units
HP96T/YNU-A
-
-
48 - 144
24
HP120T/YNU-A
-
-
60 - 180
30
HP144T/YSNU-A
HP72T/YNU-A
HP72T/YNU-A
72 - 216
36
HP192T/YSNU-A
HP96T/YNU-A
HP96T/YNU-A
96 - 288
48
HP240T/YSNU-A
HP120T/YNU-A
HP120T/YNU-A
120 - 360
50
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......