[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
HWE18220_GB
chapter 7 -
49
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-8-6
Error Code [6603]
1. Error code definition
Transmission line bus busy error
2. Error definition and error detection method
Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busy
Generated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise
Detail code 001: Transmission Bus-Busy error in centralized control system
Detail code 002: Transmission Bus-Busy error in indoor unit system
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc-
curred.
3. Cause, check method and remedy
7-8-7
Error Code [6606]
1. Error code definition
Communication error between device processor and transmission processor or M-NET processor
2. Error definition and error detection method
Communication error between device processor on circuit board and transmission processor or M-NET processor
Detail code 003: Communication error between device processor on circuit board and M-NET processor
The address/attribute appeared on the display on the remote controller indicates the controller where an error oc-
curred.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
The transmission processor cannot be transmit-
ted as the short-wavelength voltage like noise ex-
ists consecutively on the transmission line.
Check the transmission wave shape and noise on the
transmission line.
Refer to the following page(s). [8-4 Checking Transmis-
sion Waveform and for Electrical Noise Interference]
ĺ
No noise indicates that the error source controller is a
failure.
ĺ
If noise exists, investigate the noise.
(2)
Error source controller failure
Cause
Check method and remedy
(1)
Data is not properly transmitted due to accidental
erroneous operation of the controller of the error
source.
Turn off the power source of the outdoor and the indoor
units.(When the power source is turned off separately, the
microcomputer will not be reset, and the error will not be
corrected.)
ĺ
If the same error occurs, the error source controller is
a failure.
(2)
Error source controller failure
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......