[2-10 Restrictions on Refrigerant Pipes ]
38
-
chapter 2
HWE18220_GB
2 Restrictions
2-10-2
Restrictions on Refrigerant Pipe Size
(1) Between outdoor unit and BC controller (Part A)
*1 When the high pressure pipe exceeds 65 meters, the pipe diameter of the section exceeding 65 meters should be 28.58
[1-1/8"].
(2) Between BC controller and indoor units (Sections a, b, c, d, e, f, g, i, j, k, m, and n)
(3) Between the main and sub BC controllers (Sections F, G, J, and K)
Unit : mm [inch]
Outdoor units
High-pressure pipe
Low-pressure pipe
HP72
ø15.88 [5/8"]
ø19.05 [3/4"]
HP96
ø19.05 [3/4"]
ø22.2 [7/8"]
HP120
ø28.58 [1-1/8"]
HP144
ø22.2 [7/8"]
HP192
HP240
ø22.2 [7/8"]
*1
ø34.93 [1-3/8"]
Unit : mm [inch]
Indoor unit
Liquid pipe
Gas pipe
P05 - P18
ø6.35 [1/4"]
ø12.7 [1/2"]
P24 - P54
ø9.52 [3/8"]
ø15.88 [5/8"]
P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P96
ø9.52 [3/8"]
ø22.2 [7/8"]
Unit : mm [inch]
Total capacity of downstream indoor
units
High-pressure gas pipe
Low-pressure gas pipe
Liquid pipe
- P72
ø15.88 [5/8"]
ø19.05 [3/4"]
ø9.52 [3/8"]
P73 - P108
ø19.05 [3/4"]
ø22.2 [7/8"]
P109 - P126
ø28.58 [1-1/8"]
ø12.7 [1/2"]
P127 - P144
ø22.2 [7/8"]
P145 - P180
ø15.88 [5/8"]
P181 - P234
ø28.58 [1-1/8"]
P235 - P288
ø34.93 [1-3/8"]
ø19.05 [3/4"]
P289 - P360
ø41.28[1-5/8"]
P361 -
ø34.93 [1-3/8"]
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......