[8-9 Troubleshooting Problems with Major Components on BC Controller ]
HWE18220_GB
chapter 8 -
43
8 Troubleshooting Based on Observed Symptoms
8-9-5
BC Controller Transformer
* Before measuring the resistance, pull out the connector.
Normal
Abnormal
CNTR(1)-(3)
about 58
ȍ
.
Open-phase or shorting
CN03(1)-(3)
about 1.6
ȍ
.
CNTR
CN03
BC controller control board
Red
White
Red
Red