[5-2 Outdoor Unit Control ]
18
-
chapter 5
HWE18220_GB
5 Control
2) When combination of units
For a combination of units, operation is split so that there is a unit for defrosting and a unit for the heating operation. If one of
the combination of units is operated, the stopped unit is started, the unit that was operating is defrosted, and then the unit that
was stopped before the control began is defrosted. At that time, operation by the outdoor units that make up the combination
is as shown in the table below.
*1 The valve will turn off if TH4>80°C is met while defrosting of the second unit is performed while the unit is in operation.
(3) Continuous heating mode end conditions
Continuous heating mode will end when the Continuous heating mode time in the table below is reached.
When the Continuous heating mode ends, the frequency is reduced once.
Unit in defrost cycle
Unit in operation
Outdoor unit fan 1
Stopped
In operation
Outdoor unit fan 2
Stopped
In operation
SV1a
ON
*1
OFF
SV2
ON
*1
OFF
LEV2a
1000
According to refrigerant
equalization control
LEV2b
1000
According to refrigerant
equalization control
LEV2c
-
LEV2d
6000
According to refrigerant
equalization control
21S4a
OFF
ON
21S4b
OFF
ON
21S4c
-
Single unit
Combination units
Continuous heating mode time
When 10 minutes have passed When 10 minutes have passed
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......