[5-2 Outdoor Unit Control ]
24
-
chapter 5
HWE18220_GB
5 Control
5-2-16
Operation Mode
(1) Indoor unit operation mode
The operation mode can be selected from the following 6 modes using the remote controller.
(2) Outdoor unit operation mode
When units in cooing and heating coexist, the operation mode (cooling main mode or heating main mode) will be determined,
based on the refrigerant pressure in the R2 refrigerant circuit and speed variation data.
(3) Operation pattern for automatic cooling/heating mode
When the automatic cooling/heating mode is selected from remote controller functions, the indoor temperature will be detect-
ed in pattern as shown in the figure below, and the operation mode (cooling or heating) will automatically be selected.
(4) Relationship between the operation mode and the load capacity (kW) (within a system)
1
Cooling mode
2
Heating mode
3
Dry mode
4
Automatic cooling/heating
mode
5
Fan mode
6
Stopping mode
1
Cooling only mode
All indoor units in operation are in cooling mode.
2
Heating only mode
All indoor units in operation are in heating mode.
3
Cooling main mode
Coexistence of units in cooling and heating modes.
4
Heating main mode
Coexistence of units in cooling and heating modes.
5
Stopping mode
All indoor units are in fan mode or stopping mode.
+1.5ºC
+0.5ºC
-0.5ºC
-1.5ºC
Set temp
+1ºC
-1ºC
Cooling
3 minutes
3 minutes
Switches to cooling mode
Switches to heating mode
Cooling
Cooling
Cooling
Cooling
Heating
Heating
Heating
Fan
Fan
Fan
Fan
Fan
Fan
Fan
When it detects more than 1.5 degrees difference against set temperature for more
than 3-min continuously, operation mode change to cooling mode.
*If it comes under 1.5 degrees difference again, it need to count 3 minutes from at that time.
When it detects more than 1.5 degrees difference against set temperature
for more than 3-min continuously, operation mode change to heating mode.
*If its over 1.5 degrees difference again, it need to count 3 minutes from that time.
Cooling load
capacity
Heating load
capacity
+
Cooling load
capacity
Heating load
capacity
Heating load
capacity
+
Cooling load
capacity
100(%)
Cooling only
mode
Cooling main
mode
Heating main
mode
Total heat recovery mode
Heating only
mode
100(%)
Heating
load (%)
Heating load
X100 = Cooling
load (%)
=
Cooling load
X 100
0
0
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......