[2-10 Restrictions on Refrigerant Pipes ]
HWE18220_GB
chapter 2 -
43
2 Restrictions
*1 When the high pressure pipe exceeds 65 meters, the pipe diameter of the section exceeding 65 meters should be 28.58
[1-1/8"].
Unit : mm [inch]
Outdoor units
High-pressure side
Low-pressure pipe
Outdoor unit side
HP72
ø15.88 [5/8"] (Brazed connection)
ø19.05 [3/4"] (Brazed connection)
HP96
ø19.05 [3/4"] (Brazed connection)
ø22.2 [7/8"] (Brazed connection)
HP120
ø28.58 [1-1/8"] (Brazed connection)
HP144
ø22.2 [7/8"] (Brazed connection)
HP192
HP240
ø22.2 [7/8"]
*1
(Brazed connection)
ø34.93 [1-3/8"] (Brazed connection)
Indoor unit side
ø9.52 [3/8"] (Brazed connection)
ø15.88 [5/8"] (Brazed connection)