[2-7 Example System with an MA Remote Controller ]
HWE18220_GB
14
-
chapter 2
2 Restrictions
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor
units (OC and OS), of the terminal block for indoor-out-
door transmission line (TB02) on the main BC controller
(BC), and of the terminal block for indoor-outdoor trans-
mission line (TB5) on each indoor unit (IC). (Non-polar-
ized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are au-
tomatically designated as OC and OS in the order of ca-
pacity from large to small (if two or more units have the
same capacity, in the order of address from small to
large).
Shielded cable connection
Daisy-chain the ground terminal (
) on the outdoor
units (OC and OS), the S terminal of the terminal block
(TB02) on the BC controller (BC), and the S terminal of
the terminal block (TB5) on the indoor unit (IC) with the
shield of the shielded cable.
2) Transmission line for centralized control
No connection is required.
3) MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the
terminal block on the MA remote controller (MA).
(Non-polarized two-wire)
When 2 remote controllers are connected to the sys-
tem
When 2 remote controllers are connected to the system,
connect terminals 1 and 2 of the terminal block (TB15) on
the indoor unit (IC) to the terminal block on the two MA
remote controllers.
Set one of the MA remote controllers as a sub controller.
(Refer to the Instruction Manual for the MA remote con-
troller for the setting method.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy-
chain terminals 1 and 2 on the terminal block (TB15) on
all indoor units (IC) in the same group, and then connect
terminals 1 and 2 on the terminal block (TB15) on the in-
door unit on one end to the terminal block on the MA re-
motecontroller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor ad-
dresssetup" is not available.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal
block(TB5) on the indoor unit (IC) to the appropriate ter-
minals on the terminal block (TB5) on LOSSNAY (LC).
(Non-polarized two-wire)
Interlock operation setting with all the indoor units in the
same system will automatically be made. (It is required
that the Lossnay unit be turned on before the outdoo-
runit.)
For information about certain types of systems (1. Sys-
tems in which the LOSSNAY unit is interlocked with only
part of the indoor units, 2. Systems in which the LOSS-
NAY unit is operated independently from the indoor
units, 3. Systems in which more than 16 indoor units are
interlocked with the LOSSNAY unit, and 4. Systems to
which two ore more LOSSNAY units are connected), re-
fer to the following page(s). [2-7-2 Single Refrigerant
System with Two or More LOSSNAY Units]
5) Switch setting
6) When replacing the control board on only some of the
outdoor units, delete all connection information. (Refer to
[5-1-1 Outdoor Unit Switch Functions and Factory Set-
tings] for information on switch functions.)
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
Proce-
dures
Unit or controller
Address set-
ting range
Setting method
Notes
Factory
setting
1
Indoor unit
Main unit
IC
No settings
required.
-
Port number setting is re-
quired
For information about how to
perform a group operation of
indoor units that feature dif-
ferent functions, refer to the
following page(s). [2-7-2
Single Refrigerant System
with Two or More LOSSNAY
Units]
00
Sub unit
IC
2
LOSSNAY
LC
No settings
required.
-
00
3
MA
remote con-
troller
Main
remote con-
troller
MA
No settings
required.
-
Main
Sub
remote con-
troller
MA
Sub
remote con-
troller
Settings to be
made with the
Sub/Main
switch
4
Outdoor unit
OC
OS
No settings
required.
-
00
5
Auxiliary
outdoor unit
BC
controller
BC
No settings
required.
-
00
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......