[2-7 Example System with an MA Remote Controller ]
HWE18220_GB
chapter 2 -
17
2 Restrictions
2-7-3
Grouped Operation of Units in Separate Refrigerant Circuits
(1) Sample control wiring
(2) Cautions
1) ME remote controller and MA remote controller cannot both
be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to
a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units
that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must
be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for
transmission line for centralized control (TB7) on only one of
the outdoor units.
6) When the number of the connected indoor units is as shown
in the table below, one or more transmission boosters (sold
separately) are required.
To connect two transmission boosters, connect them in par-
allel. (Observe the maximum number of connectable indoor
units that are listed in the specifications for each outdoor
unit.)
The table above shows the number of transmission
boosters that is required by the system with three BC
controllers. For each BC controller added or subtracted,
subtract or add two indoor units.
Refer to the DATABOOK for further information about
how many booster units are required for a given system.
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
[AWG16] or larger)
L11+L12
200m [656ft]
L21+L22
200m [656ft]
2) Transmission line for centralized control
L31+L21
200m [656ft]
3) MA remote controller wiring
Same as 2-7-1
4) Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L12(L11)+L31+L22(L21)
1000 m [3280ft] (500 m
[1640ft])
*1
*1 If a given system includes one or more unit or remote
controller that does not support the maximum allow-
able cable distance of 1000 m [3280 ft], the maximum
allowable cable distance in the system will be 500 m
[1640 ft]. Refer to the latest catalog for information on
which units and remote controllers support the maxi-
mum allowable cable distance of 1000 m [3280 ft].
IC
TB5
S
TB15
1 2
01
IC
TB5
S
TB15
1 2
03
A1 B2
MA
A1 B2
MA
LC
TB5
S
07
IC
TB5
S
1 2
TB15
IC
TB5
S
TB15
1 2
1 2
04
02
IC
TB5
TB15
S
05
A1 B2
MA
Group
IC
TB5
S
TB15
1 2
06
A1 B2
MA
Group
Group
Group
To be left
unconnected
m2
m3
Interlock operation with
the ventilation unit
L12
L22
L11
L21
OC
Move the male connector
from CN41 to CN40.
SW5-1 OFF
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
Leave the male
connector on
CN41 as it is.
SW5-1 OFF
TB3
TB7
S
51
OS
TB3
TB7
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
M1 M2
S
52
OC
TB3
TB7
S
55
OS
TB3
TB7
S
56
L31
To be left
unconnected
S
S
BC
TB02
53
BC
TB02
57
To be left
unconnected
To be connected
m1
m4
m5
Number of transmission boost-
er (sold separately) required
1 unit
2 units
When the P72 and P96 models are
not included in the connected indoor
units
27 - 50 units
-
When the P72 and P96 models are in-
cluded in the connected indoor units
21 - 39 units
40 - 50 units
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......