[7-8 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
66
-
chapter 7
HWE18220_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-8-25
Error Code [6846]
1. Error code definition
Start-up time over
2. Error definition and error detection method
Start-up time over The unit cannot finish start-up process within 4 minutes after power on.
3. Cause, check method and remedy
Note: Refer also to the Service Handbook for the indoor units.
Cause
Check method and remedy
(1)
Contact failure of indoor/outdoor unit connecting wire
Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of in-
door and outdoor units.
(2)
Diameter or length of indoor/outdoor unit connecting wire is out
of specified capacity.
Check the following: Diameter of the cables
used for indoor-outdoor lines; maximum line
distance between indoor and outdoor units
(max. 50 m); maximum line distance be-
tween indoor units (daisy-changed cables)
(max. 30 m); and if flat cables such as VVF is
used, make sure they are connected in the
order of S1, S2, and S3.
(3)
2 or more outdoor units have refrigerant address "0". (In case of
group control)
When units are controlled as groups, check
the refrigerant address (SW1 (3-6) on the
outdoor unit control board settings) for dupli-
cates.
(4)
Noise has entered into power supply or indoor/outdoor unit con-
necting wire.
Check the transmission lines for problems.
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......