[8-13 Parts Replacement Instructions ]
HWE18220_GB
chapter 8 -
91
8 Troubleshooting Based on Observed Symptoms
(18) To remove the front heat exchanger, first remove the front, left, right, and center frames by unscrewing the 14 screws.
(See Figure 14.)
To remove the rear heat exchanger, remove the rear frame in addition to the front, left, right, and center frames by
unscrewing the 16 screws. (See Figure 14.)
(19) Unscrew the two screws each on the right and left panels. (See Figure 15 Right and Left.)
(20) Remove the left front pillar by unscrewing the 9 screws. (See Figure 15 Front and Left.)
(21) Remove the right front pillar by unscrewing the 5 screws. (See Figure 15 Front and Right)
*Use the supplied spacers. Use the spacers 60 (D) X 250 (W) X 60 (H) when replacing the heat exchangers for the maintenance of the
accumulator and the pipes.
Right frame
Front frame
Left frame
Left front pillar
Right front pillar
Left panel
Right panel
Spacer *
Figure 15 Front
Figure 15 Left
Figure 15 Right
Center frame
Figure 14
Rear frame
Connection of the pillar to the rear heat exchanger (4 screws)