[2-7 Example System with an MA Remote Controller ]
HWE18220_GB
chapter 2 -
25
2 Restrictions
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS.
They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
Pro-
ce-
dur
es
Unit or controller
Address
setting
range
Setting method
Notes
Fac-
tory
set-
ting
1
Indoor
unit
Main unit IC
01 to 50
Assign the smallest address to the main unit in the
group.
In a system with a sub BC controller, make the set-
tings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC control-
ler
(ii) Indoor unit to be connected to sub BC controller 1
(iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that
the formula "(i) < (ii) < (iii)" is true.
When using additional BC controllers (3 to 11 BC
controllers), make the same settings.
Port number setting is re-
quired
To perform a group opera-
tion of indoor units that
feature different functions,
designate the indoor unit
in the group with the
greatest number of func-
tions as the main unit.
00
Sub unit
Assign sequential numbers starting with the address of
the main unit in the same group +1. (Main unit address
+1, main unit a2, main unit a3, etc.)
2
LOSSNAY
LC
01 to 50
Assign an arbitrary but unique address to each of these
units after assigning an address to all indoor units.
None of these addresses may
overlap any of the indoor unit ad-
dresses.
00
3
MA
remote
control-
ler
Main re-
mote
controller
MA
No set-
tings re-
quired.
-
Make the same indoor unit group
settings with the system controller
as the ones that were made with
the MA remote controller.
Mai
n
Sub re-
mote con-
troller
MA
Sub re-
mote
controller
Settings to be made with the Sub/Main switch
4
Outdoor unit
OC
OS
51 to 100
The sum of the smallest address of the indoor units in
the same system and 50.
Assign sequential address to the outdoor units in the
same refrigerant circuit.
The outdoor units are automatically designated as
OC and OS.(Note)
To set the address to 100, set
the rotary switches to 50.
00
5
Auxilia-
ry unit
BC con-
troller
(Main)
BC
51 to 100
OC (or OS if it exists) +1
To set the address to 100, set
the rotary switches to 50.
If the addresses that is assigned
to the main BC controller over-
laps any of the addresses that
are assigned to the outdoor
units or to the sub BC control-
ler, use a different, unused ad-
dress within the setting range.
The use of a sub BC controller
requires the connection of a
main BC controller.
00
BC
controller
(Sub)
BS
51 to 100
Assign an address that equals the sum of the smallest
address of the indoor units that are connected to the
sub BC controller and 50.
Summary of Contents for PURY-HP144
Page 1: ......
Page 9: ...viii ...
Page 13: ...HWE18220_GB ...
Page 29: ...HWE18220_GB ...
Page 77: ...HWE18220_GB ...
Page 95: ...HWE18220_GB ...
Page 125: ...HWE18220_GB ...
Page 153: ...HWE18220_GB ...
Page 163: ...HWE18220_GB ...
Page 343: ...HWE18220_GB ...
Page 361: ...HWE18220_GB ...
Page 398: ......