[7-6 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
34
-
chapter 7
HWE18220_GB
7 T
ro
ublesh
ootin
g Using Err
o
r Co
des
7-6-23
Error Codes [4250, 4255, 4256] Detail Code 105
1. Error code definition
Overcurrent error due to short-circuited motor (Detail code 105)
2. Error definition and error detection method
When a short is detected on the load side just before starting the inverter operation.
3. Cause, Check method and remedy
In the case of 4250
In the case of 4255 and 4256
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems]
Cause
Check method and remedy
(1)
Short - circuited compressor
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault
and Coil Resistance Problems]
(2)
Output wiring
Check for a short circuit.
Cause
Check method and remedy
(1)
Short - circuited fan motor
Refer to the following page(s).
[8-10-6 Checking the Fan Motor for Ground Fault
and Coil Resistance Problems]
(2)
Output wiring
Check for a short circuit.