M800/M80/E80 Series Maintenance Manual
3 Maintenance of the Drive Unit
56
IB-1501273-F
Replacement procedure
Replace the unit fan with the following procedures.
<MDS-E/EH-V1/V2/V3/SP/SP2 Series>
(1) Turn the breaker for the input power OFF, and wait for the CHARGE lamp on the power supply unit to turn OFF before
removing the unit.
(2) Remove the fan guard from the back of the drive unit, and remove the two fan mounting screws.
(3) Remove the fan power cable.
(4) Disconnect the connection connector, and replace the fan.
POINT
When the drive unit of E/EH Series which uses two cooling fans is in an emergency stop or alarm, one of fans (upper
one in the case of vertical layout, or either one in the case of horizontal layout) is stopped and power-saving oper-
ation is performed. If the suspended fan is restarted by canceling the emergency stop, it is not a problem with the
fan.
Remove the two screws.
Pull out the connection
connector and disconnect
the connector.
Summary of Contents for E80 Series
Page 1: ......
Page 7: ......
Page 17: ......
Page 19: ......
Page 21: ......
Page 23: ......
Page 25: ......
Page 28: ...1 1 IB 1501273 F System Basic Configuration ...
Page 68: ...2 41 IB 1501273 F Daily Maintenance and Periodic Maintenance ...
Page 78: ...3 51 IB 1501273 F Maintenance of the Drive Unit ...
Page 101: ...M800 M80 E80 Series Maintenance Manual 3 Maintenance of the Drive Unit 74 IB 1501273 F ...
Page 102: ...4 75 IB 1501273 F Failure Diagnosis ...
Page 165: ...M800 M80 E80 Series Maintenance Manual 4 Failure Diagnosis 138 IB 1501273 F ...
Page 166: ...5 139 IB 1501273 F Troubleshooting ...
Page 169: ...M800 M80 E80 Series Maintenance Manual 5 Troubleshooting 142 IB 1501273 F ...
Page 170: ...6 143 IB 1501273 F Replacing Each Unit ...
Page 205: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 178 IB 1501273 F ...
Page 212: ......