M800/M80/E80 Series Maintenance Manual
4 Failure Diagnosis
89
IB-1501273-F
(*1) As for the NC unit, the contents are as follows depending on the condition:
NC
Communication between NC unit and display unit
Item
Details
Battery vol state
This displays the current state of the battery voltage as 0 or 1.
Condition
Class
0 (normal state)
-
1 (encoder error)
(no battery)
Warning (yellow)
Battery used years
This displays approximate time of the battery used from the last replacement.
Condition
Class
Recommended battery use (5 years) <= Time for the bat-
tery used
Warning (yellow)
NC : temp. 1 (°C)
This displays the current temperature of the control unit.
Condition (M800S: Main card /M80/E80)
Class
78.5°C < Control unit temp. <= 81°C
Caution (gray)
81°C < Control unit temp.
Warning (yellow)
Condition (M800W: Main card)
Class
79°C < Control unit temp. <= 84.5°C
Caution (gray)
84.5°C < Control unit temp.
Warning (yellow)
Condition (M80W: Main card)
Class
79°C < Control unit temp. <= 81.5°C
Caution (gray)
81.5°C < Control unit temp.
Warning (yellow)
Fan rev (r/min)
This displays the current fan rotation speed of the control unit.
Condition
Class
Fan rot. speed <= 4000 r/min
Warning (yellow)
Item
Details
Servo comm err Num1
This displays the count of occurrence for "Y51 SV commu er: Recv frame No. xx04"
after the power ON.
Servo comm err Acc1
This displays the cumulated count of occurrence for " Y51 SV commu er: Recv
frame xx04".
Press the menu [Servo clear] to clear the cumulated count to "0".
Servo comm err Num2
This displays the count of occurrence for "Y51 SV commu er: Data ID error xx03"
after the power ON.
Servo comm err Acc2
This displays the cumulated count of occurrence for "Y51 SV commu er: Data ID er-
ror xx03".
Press the menu [Servo clear] to clear the cumulated count to "0".
RIO channel/station1
This displays the Channel No./Station No. of occurrence for continuous error after
the power ON.
RIO retry count max 1
This displays the maximum value of the continuous error after the power ON.
RIO channel/station 2
This displays the Channel No./Station No. held even if the power OFF.
Press the menu [RIO clear] to clear the Channel No./Station No. to "0/0".
RIO retry count max 2
This displays the count held even if the power OFF.
Press the menu [RIO clear] to clear the count to "0".
Ether comm err Num
This displays the number of Ethernet communication error after PLC program is ex-
ecuted once.
Ether comm err Acc
This displays the cumulated count of occurrence for Ethernet communication error.
Press the menu [Ether clear] to clear the cumulated count to "0".
Overvoltage Acc
This displays the cumulated count of detection frequency of overvoltage after the
power ON.
Press the menu [Cl. ov.history] to clear the cumulated count to "0".
Power losses Num
This displays the count of detection frequency of instantaneous power interruption
after the power ON.
Summary of Contents for E80 Series
Page 1: ......
Page 7: ......
Page 17: ......
Page 19: ......
Page 21: ......
Page 23: ......
Page 25: ......
Page 28: ...1 1 IB 1501273 F System Basic Configuration ...
Page 68: ...2 41 IB 1501273 F Daily Maintenance and Periodic Maintenance ...
Page 78: ...3 51 IB 1501273 F Maintenance of the Drive Unit ...
Page 101: ...M800 M80 E80 Series Maintenance Manual 3 Maintenance of the Drive Unit 74 IB 1501273 F ...
Page 102: ...4 75 IB 1501273 F Failure Diagnosis ...
Page 165: ...M800 M80 E80 Series Maintenance Manual 4 Failure Diagnosis 138 IB 1501273 F ...
Page 166: ...5 139 IB 1501273 F Troubleshooting ...
Page 169: ...M800 M80 E80 Series Maintenance Manual 5 Troubleshooting 142 IB 1501273 F ...
Page 170: ...6 143 IB 1501273 F Replacing Each Unit ...
Page 205: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 178 IB 1501273 F ...
Page 212: ......