M800/M80/E80 Series Maintenance Manual
4 Failure Diagnosis
90
IB-1501273-F
(*2) The following state can be confirmed.
Power losses Acc
This displays the cumulated count of detection frequency of instantaneous power
interruption after the power ON.
Press the menu [Clear pw loss] to clear the cumulated count to "0".
State
Details
In-position
This displays "1" (in-position state) when the following conditions are satisfied for
even one axis.
There is a control axis whose acceleration/deceleration is not zero.
There is a control axis whose servo error exceeds the range designated with the
parameter.
Interlock (+)
When the auto intn-th axis signal or the manual intn-th axis signal
is OFF, "1" appears for the n-th axis.
In the above case, the 2nd axis is interlocked. Even when the number of usable
axes is less than 8 in 1 part system, this displays 8 axes fixed.
Interlock (-)
When the auto interlock -n-th axis signal or the manual interlock -n-th axis signal is
OFF, "1" appears for the n-th axis.
The explanation of the display is same as for the "Interlock (+)".
ExtDcc (+)
When the control axis is moving in (+) direction, "1" appears for the axis if the exter-
nal deceleration speed is valid, and the feedrate is clamped, exceeding the set value
of the external deceleration speed.
In the above case, the 1st axis and the 3rd axis are in external deceleration speed.
Even when the number of usable axes is less than 8 in 1 part system, this displays
8 axes fixed.
ExtDcc (-)
When the control axis is moving in (-) direction, "1" appears for the axis if the exter-
nal deceleration speed is valid, and the feedrate is clamped, exceeding the set value
of the external deceleration speed.
The explanation of the display is same as for the ")".
Menus
Menus
Details
This clears the cumulated count of the servo communication error 1 and 2 to "0".
This clears the cumulated count of the RIO communication error to "0".
This clears the cumulated count of the Ether communication error to "0".
This clears the time the battery has been used to "0".
This clears the accumulated number of instantaneous power interruption detection times to "0".
This clears the cumulated count of overvoltage to "0".
Item
Details
(Explanation of the display)
o o o o o o 1 o
8th axis
…
1st axis
(Explanation of the display)
o o o o o 1 o 1
8th axis
…
1st axis
Servo
clear
RIO
clear
Ether
clear
Battery
clear
Clear
pw loss
Cl. ov.
history
Summary of Contents for E80 Series
Page 1: ......
Page 7: ......
Page 17: ......
Page 19: ......
Page 21: ......
Page 23: ......
Page 25: ......
Page 28: ...1 1 IB 1501273 F System Basic Configuration ...
Page 68: ...2 41 IB 1501273 F Daily Maintenance and Periodic Maintenance ...
Page 78: ...3 51 IB 1501273 F Maintenance of the Drive Unit ...
Page 101: ...M800 M80 E80 Series Maintenance Manual 3 Maintenance of the Drive Unit 74 IB 1501273 F ...
Page 102: ...4 75 IB 1501273 F Failure Diagnosis ...
Page 165: ...M800 M80 E80 Series Maintenance Manual 4 Failure Diagnosis 138 IB 1501273 F ...
Page 166: ...5 139 IB 1501273 F Troubleshooting ...
Page 169: ...M800 M80 E80 Series Maintenance Manual 5 Troubleshooting 142 IB 1501273 F ...
Page 170: ...6 143 IB 1501273 F Replacing Each Unit ...
Page 205: ...M800 M80 E80 Series Maintenance Manual 6 Replacing Each Unit 178 IB 1501273 F ...
Page 212: ......