MI 3290 Earth Analyser
Appendix F - The balancing procedure
161
Balancing procedure will return:
r
1
= 32 m and r
2
= 139 m
The user has to decide on which position he will put the S probe.
Usually the S
B1
position is used but if this position is already within the irregular area (to close to
tested object), then the S
B2
position can be used but this requires longer cables.
3. Balancing Example
The flex clamp(s) have to be positioned
first and then the parameters have to be
entered. Balancing is enabled only in
single Test Mode.
The appropriate values for number of flex
turns have to be entered.
Select the Distance (R) parameter.
With the help of the Virtual keyboard,
enter the Distance (R) value.
(only value, no unit)
The entered value must be between 10
and 500 (only numbers), otherwise error
message will appear on screen during
balancing procedure.
Starts balancing procedure
(measurement).
(Balancing is enabled only in single Test
Mode.)
Balancing procedure running.