MI 3290 Earth Analyser
Tests and Measurements
105
Figure 11.76: Example of Potential
measurement result (X-Y)
Figure 11.77: Example of Potential
measurement result (GPS)
Notes:
Consider displayed warnings when starting the measurement!
High noise currents and voltages in earth could influence the measurement results. The
tester displays the
“noise” warning in this case.
Graph view is not available during the measurement.
Notes (Probes):
High impedance of S and H probes could influence the measurement results. In this
case,
“Rp” and “Rc” warnings are displayed. There is no pass / fail indication in this
case.
Probes must be placed at a sufficient distance from the measured object.