MI 3290 Earth Analyser
Tests and Measurements
113
11.10 Voltage [V]
Voltage / frequency Measurement
Test
Mode
Measuring
frequency
Filter
Max. Measuring
range
Uh, Us, Ues, f
Voltage Meter RMS
cont.
40 Hz – 4,5 kHz RMS
55 V
Table 11.94: Available Voltage RMS measurements in the MI 3290
Voltage Meter RMS
This function is intended for measurement of voltage noise using H, S, ES to E connection
terminals.
H
S
ES
E
MI 3290 Earth Analyser
V
S - probe
H - auxiliary
current probe
E a r t h
H
S
ES
E
V
V
Figure 11.95: Voltage Meter RMS example
11.10.1 Voltage Meter RMS Measurement
Test can be started from the Voltage Meter RMS measurement window.
Figure 11.96: Example of Voltage Meter RMS measurement result
Voltage Meter RMS measurement procedure:
Select the Voltage Meter RMS measurement function.
Connect the instrument to the test object.
Press the Run key to start the measurement.
Wait until the test result is displayed on the screen.
Press the Run key to stop the measurement.
Save results (optional).
Notes:
Frequency is measured on the terminal with highest measured voltage.
Consider displayed warnings when starting the measurement!