84
ZERO TARE ALARM
(former: DUMP ALARM)
ALARM CODE:15
Problem: Load Cells outside of acceptable Calibration.
Weigh bin empty weigh above tare high upper limit (TH parameter) or
below tare lower limit (TL parameter). If above TH (upper limit) weigh
bin dump valve opens and closes repeatedly. Possible causes:
There is material in the weigh bin that will not dump out.
The dump flap may be stuck.
The load cells are hung up or obstructed.
The load cells are out of calibration.
Solution:
Clear material jam, check dump valve for free movement,
Check that weigh bin and load cells are free from contact with door and
back of enclosure, verify weigh bin is installed correctly. If weigh bin is
empty and weight reading on-screen is above TH parameter or below
TL parameter then recalibration load cells. See page 32 (zero only)
and 68 (zero and full calibration).
OVER WEIGHT ALARM
ALARM CODE:20
Problem: Over Dispense triggered by Alarm Parameter
First three digits of the component specific AL parameter (
000
00) are
used to STOP and ALARM the blender if an over dispense occurs by a
specified number of grams or percent.
Grams:
enter 001 to 499 in the
first three digits.
Percent:
enter the number “5” in the first digit. When
percent is enabled, the 2
nd
and 3
rd
digits are the percent (01 – 99). In
the first digit of the _AL parameter, 6 – 9 are invalid digits.
Solution:
Determine
cause of over dispense.
WAIT FOR RECIPE ALARM
ALARM CODE:21
Problem: Recipe Request option did not receive a
recipe within the 2 minute timeout period.
When enabled the Recipe Request option uses the Recipe Number
Tag to request a recipe over communications. If the recipe number is
changed to a value between 100 - 65535, the 2-minute Recipe
Request timer starts and monitors for a change in the recipe. If a
recipe is not received within the timeout period, this alarm sounds.
Solution:
Check Recipe number, check status of communications.
WEIGHT DROP ALARM
ALARM CODE:22
Problem: Weigh Bin loosing weight during a cycle.
This alarm is triggered by a loss of more than 20 grams during a
dispense cycle. This serves to detect and report a weigh bin problem,
such as material leaking from the bottom of the bin.
Solution:
Examine weigh bin for issues with material retention such as
weigh bin flap closure problems, material jam, angel hair causing leak,
low air pressure, damage to weigh bin or obstruction to weigh bin
closing.
MCT PARAMETER ALARM
ALARM CODE:23
Problem: Cycle time exceeds previous cycle time by
value set in MCT parameter.
The MCT parameter when used, monitors sequential cycle times and
alarms if a cycle time exceeds the previous cycle time by an amount
that is not consistent with proper operation. See: MCT parameter.
Solution:
Check material source. MCT parameter alarm may indicate
a problem with material loading, blending issues or delays in
completing a cycle such as vibration.
Summary of Contents for FLEXBUS Lite
Page 6: ...6...
Page 10: ...10 Blender Parts Key...
Page 13: ...13...
Page 100: ...100 Technical Drawings...
Page 101: ...101...
Page 102: ...102...
Page 103: ...103...
Page 104: ...104...
Page 105: ...105...
Page 106: ...106...
Page 107: ...107...
Page 108: ...108...
Page 109: ...109...
Page 110: ...110...
Page 111: ...111...
Page 112: ...112 FCA INSTALLATIONDIAGRAM...
Page 113: ...113 WSB 4088 IO wiring diagram 120V...
Page 114: ...114 D WSB E0001 Electrical Diagram WSB Export Single Phase...
Page 115: ...115 D WSB E0002 Electrical Diagram WSB Export 3 Phase...
Page 116: ...116 D WSB E0003 Electrical Diagram WSB Export 1800 3 Phase...
Page 117: ...117 D WSB E0004 Electrical Diagram WSB Export Maxibatch...
Page 118: ...118 D WSB P0001 Pneumatic Diagram WSB with Non Removable Hoppers...
Page 119: ...119 D WSB P0002 Pneumatic Diagram WSB with Removable Hoppers...
Page 120: ...120...
Page 138: ...138 Flexbus Lite Wiring Diagrams...
Page 139: ...139...
Page 140: ...140 Flexbus Lite Component Map...